Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 10/04/2000 | ELECTRIC - FINAL | Denied | INSTALL REJECTION CLIPS IN FUSED DISCONNECT SWITCHES AT SERVICE COULD NOT INSPECT AT LAST INSPECTION NO KEYS TO LOCKS LABELS NEED TO BE PERMANENT NOT MARKER 230-70 N.E.C. AND CITY OF TUCSON ORDINANCE # 9287 |
|
| 10/02/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* BLDG # 1500- SUPPORT 1/2" CONDUIT WITHIN 3' OF J-BOXES BLDG # 11 &1200 LABEL BREAKER PANELS BLD # 1600- " " LABEL PANELS OUTSIDE NORTH WEST BLDG #10 LABEL DISCONNECTS SWITCHES AT MAIN SERVICE |
|
| 07/14/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* BLDG 1,2,3,9 C OF O |