Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 07/26/2000 |
PLUMBING - INTERMEDIATE |
|
Approved |
|
| 07/08/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
1. WATER CLOSETS MUST HAVE MIN 15" CLEARANCE ON BOTH SIDES |
| 12/21/1999 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - DWV OK PLANS ARE CONTRADICTORY REGARDING WATER PIPING, ONE NOTE CALLS FOR TYPE K OR L. ANOTHER NOTE CALLS FOR L,M, OR PB. YOUVE USED TYPE M AND PEX, PLEASE HAVE ARCHITECT CORRECT BY THE NEXT INSPECTION WATER TEST ON PEX OK. |
| 12/21/1999 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
TESTS OK.NEED PLAN REV. |
| 12/20/1999 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. NOT READY FOR INSPECTION. |
| 12/20/1999 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |