Permit: T99CM05413

Parcel: 140191930


Addresses:

5482 S MINORKA PL

Inspection Status: Correction Required

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
11/19/1999 ELECTRIC - CABLE DROP Correction Required ADDTL COMMS - NEED TO CONNECT THE #4 FROM THE GROUND RODS TO THE PEDISTAL NEUTRAL ITS TIED TO THE EQUIPMENT GROUND BUS RUN A JUMPER FROM THE NEUTRAL BUS TO THE EQUIPMENT GROUND BUS AND RECALL
11/19/1999 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0000$