Permit: T99CM04827

Parcel: 112063860


Addresses:

2202 E WATER ST

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
11/29/2000 ROOF NAILING Approved IVRS - Inspection 0000*
11/27/2000 ROOF NAILING Denied IVRS - Inspection 0140*/1. ROOF SHEATHING MUST BE NAILED WITH MAXIMUM SPACING OF NAILS AT 6" ON ENDS AND SUPPORTED EDGES WITH FIRST NAIL WITHIN 1 1/2" OF EDGES AND FIELD MAXIMUM SPACING OF 12" O.C. 2. ROOF SHEATHING PANELS MUST SPAN A MINIMUM OF 2 BAYS. 3. RAFTERS.