Permit: T99CM04795

Parcel: 12407179B


Addresses:

700 E BROADWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T99CM04795

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2006 MECHANICAL - INTERMEDIATE Approved APPROVING TO SATISFY PERMITS FROM 2000.
NEED TO HAVE SPRINKLER PIPING MOVED TO ACCESS FIRE DAMPERS IN UPPER PART OF RIM.
08/10/2000 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
NEED TO HAVE ARCHITECT ENGINEER PROVIDE DETAIL DRAWING DIRECTION ON
MECHANICAL CHASE
LOCATION AND POSITION OF DAMPERS AND DUCTS LOCATED INSIDE OF RATED CHASE
CANNOT BE LOCATED WITH BACK TO BACK AS NOW EXISITING THERE IS NOT SUFFIECENT CLEARANCE FOR PROPER INSTALLATION OF FIRE DAMPER
LOCATION AND POSITION OF DAMPERS AND DUCTS LOCATED INS
08/07/2000 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
1. CHECK W/ARCH FOR RATED MECH CHASE 1ST THRU 2ND FLOOR