Permit: T99CM04130

Parcel: 141201370

Inspection Status: Correction Required

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
12/01/1999 ROOF NAILING Correction Required ADDTL COMMS - 0. SHEARWALLS REQUIRE DBL. 2X STUD AT EA. END. SEE TYPICAL SHEARWALL DETAIL. 1. ANCHOR BOLTS-SEVERAL MISSING- MUST BE WITHIN 12 OF EACH END. 2. ANCHOR BOLTS-OVERSIZE HOLE BORED IN BOTTOM PLATE. USE LARGER WASHER WHERE OVERSIZE HOLE ALLOWS WASHER (INSTALLED) TO SINK IN. 4. WIND STRAPS MUST HAVE TWO (2) NAILS AT EACH END AND AT EVERY STUD. 5. COIL STRAPS INSTALLED FOR FLOOR TO FLOOR CONNECTION ARE UNDER NAILED AT SOME LOCATIONS. 6. FIREBLOCK SOFFITT AT OUTSIDE WALL (KITCHEN). 7. CHIMNEY PLAT FORM FRAMING-STRAP EACH CORNER FROM PLAT FORM TO PLAT FORM-2 SECTIONS. 8. BEAM AT FRONT OF GARAGE NOT CAPPED WITH APPROVED SIMPSON POST CAPS 9
11/23/1999 ROOF NAILING Correction Required ADDTL COMMS - 1. ROOF-LOOSE PANELS AT FRONT-EAST, CHECK ALL ROOF SHEATHING. 2. PORCH-LEDGER AND JOISTS NOT CLIPPED PER PLAN. 3. LOOSE SHEAR/SHEATHING PANELS-FRONT ENTRY. 4. CLIPS-RSP 4-MISSING NAILING. 5. FIRE-PLACE FRAMING-NEEDS STRAPPING AT EACH PLAT FORM AND TO BEARING FRAME WORK. 6. PROVIDE POST CAP (SIMPSON) PER PLAN AT GARAGE BEAM. LEG 5? NEEDED.
11/23/1999 ROOF NAILING Denied IVRS - Inspection 0999*