Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
Permit Number - T99CM03963
Inspection Description - ELECTRIC - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/30/1999 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - PARTIAL OK TO CLEAR 1. BOND CONDUIT SLEEVE (BOTH ENDS PER 250-51 C) 2. SEREN OR RIVET LABEL AT DISCONNECT AND METER BASE AS WAS PREVIOUSLY REQUESTED | |
12/30/1999 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
12/28/1999 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - PARTIAL - OK TO CLEAR. 1. BOND CONDUIT SLEEVE (BOTH ENDS PER 250-51 C). 2. SREW OR RIVET LABEL AT DISCONNECT AND METER BASE AS WAS PREVIOUSLY REQUESTED. | |
12/28/1999 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* |