Permit: T99CM02609

Parcel: 130180920


Addresses:

2102 S MONTEZUMA AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/14/2000 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*
PRESSURE TEST OK
VALVE OK
OK FOR GAS
03/24/2000 PLUMBING - GAS PRESSURE TEST Correction Required ADDTL COMMS - 1. MUST PROVIDE AIR PRESSURE TEST MIN 10 LBS 2. GAS SHUT OFF VALVE MUST BE MIN 30 FROM APPLIANCE SEE SECTION 1211.15 UPC
03/24/2000 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0000*
12/06/1999 PLUMBING - GAS PRESSURE TEST Correction Required ADDTL COMMS - GAS TEST REQUIRES 10# FOR 15 MINUTES SECURE GAS LINE CHPT 12.UPC
12/06/1999 PLUMBING - GAS PRESSURE TEST Denied 10#TEST REQD, SEC.LINE