Permit: T99CM01110


Addresses:

1255 E AERO PARK BL

Inspection Status: Correction Required

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
10/20/1999 PLUMBING - YARD WTR LINE/TEST Correction Required ADDTL COMMS - 10/20/99 THE FOLLOWING ITEMS WERE THE ONLY ITEMS OBSERVED ON THIS DATE. PERFORMED AN ON-SITE OBSERVATION INSPECTION OF THE ITEM 03040 YARD LINE 20 INCH UNDERGROUND AFFF WASTE WATER PIPING INSTALLATION FROM THE PUMPING STATION AT THE SOUTHEAST CORNER OF THE HANGAR TO THE HOLDING TANK EAST OF THE SITE. THERE WERE NO THRUST BLOCKS INSTALLED AT THE VARIOUS CHANGES IN DIRECTION (AT LEAST FOUR INVOLVED). INSTRUCTED CONTRACTOR TO CONSULT WITH THE RESPONSIBLE ENGINEER CONCERNING THIS REQUIREMENT. OTHERWISE, THIS PIPING INSTALLATION WAS DETERMINED TO BE INSTALLED IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODE REQUIREMENTS. THE CONTRACTOR WAS FERFORMING A SATISFACTORY PNEUMATIC PRESSURE TEST ON THIS PIPING INSTALLATION AT HTIS TIME.PERFORMED AN ON-SITE OBSERVATION INSPECTION OF THE OVERALL EYEWASH WATER,DOMESTIC WATER, DEIONIZED WATER, COMPRESSED AIR AND BREATHING AIR PIPING WATER THROUGH THE HANGAR AND CORRIDOR AREAS.THIS PIPING IS NOW TIED TOGETHER AS A FULLY OPERATIONAL SYSTEM. THIS PIPING INSTALLATION WAS DETERMINED TO BE INSTALLED IN CONFORMANCE WITH THE CONTRACT DOCUMENTS AND APPLICABLE CODE REQUIREMENTS, THE CONTRACTOR WAS PERFORMING A SATISFACTORY HYDROSTATIC PRESSURE TEST ON THIS PIPING INSTALLATION AT THIS TIME.