Permit: T99CM00393

Parcel: 128010010

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T99CM00393

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/03/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. INSTALL BUSHING ON ALL CONDUITS W/ #4 OR LARGER WIRE 2. SERVICE IS FROM PARK MALL THEREFORE THIS SERVICE IS CONSIDERED TO BE A SUB-PANEL (REMOVE THE NEUTRAL-GROUND LINK)
12/09/1999 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*