Inspection Status: Correction Required
Inspection History: POOL/SPA PRE-GUNITE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/04/1999 |
POOL/SPA PRE-GUNITE |
|
Correction Required |
ADDTL COMMS - 1. BOND BEAM TO 1 1/2 FROM FORM. 2. SPA LIGHT SEAMS TO EXTEND IN TO LEG SPACE AS PER PLAN. 3. BOND WIRES MAY BE NEEDED FOR WROUGHT IRON FENCE. 4. MIN 20 SPLICES ( NOT SO IN A FEW AREAS) 5. GFCI TO BE MIN OF 10 FROM POOL EDGE. ALL ITEMS 1-5 HAVE BEEN COMPLETED. |