Permit: T98CM04266

Parcel: 113071090

Inspection Status: Not ready for Inspection

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/23/2000 BUILDING - FINAL Not ready for Inspection 1. SERVICE PANEL NOT PROPERLY GROUNDED. CONNECT UFER BY CONDUCTOR TO LARGE LUG OF NEUTRAL BAR. 2. RISER BONDING RING MUST BE CONNECTED TO PANEL NEUTRAL.