Inspection Status: Not ready for Inspection
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/23/2000 |
BUILDING - FINAL |
|
Not ready for Inspection |
1. SERVICE PANEL NOT PROPERLY GROUNDED. CONNECT UFER BY CONDUCTOR TO LARGE LUG OF NEUTRAL BAR. 2. RISER BONDING RING MUST BE CONNECTED TO PANEL NEUTRAL. |