Permit: T97MH00347

Parcel: 116122520


Addresses:

608 N CUESTA AV

Inspection Status: Denied

Inspection History: MOBILE HOME ELECTRICAL

Date Description Inspector Results Comments
08/29/2000 MOBILE HOME ELECTRICAL Denied 1) CONDUIT OVERFILLED. 2) 200 AMP SERVICE DISCONNECT SHOULD BE 100 AMD MAX. 3) ELECTRODE GROUNDING CONDUCTOR TO BE CLAMPED TO GROUNDING ELECTRODE. 4) HOME'S CROSS-OVER CONNECTIONS NOT INSTALLED. 5) MISSING GROUND BONDING JUMPER BETWEEN 1/2'S OF HOME. 6) SERVICE GROUND NOT PROPERLY IDENTIFIED IN SUB-PANEL. 7) NEED NAME AND LICENSE # OF LICENSED ELECTRICIAN DOING WORK.
04/16/1998 MOBILE HOME ELECTRICAL Denied NOT READY