Inspection Status: Partial Pass
Inspection History: COT - ENGR - Signage Final
| Date |
Description |
Inspector |
Results |
Comments |
| 09/21/2022 |
COT - ENGR - Signage Final |
Hthrall |
Partial Approval |
Entered by HTHRALL1 - RE: sign review
For: 2 illum wall signs + change copy on nonconforming pole sign
AT: 719 W Ajo Wy
Sign permit: T22OT00679
Reviewer: H. Thrall
Date: 09/20/22
Codes: Unified Development Code (UDC) 7A Sign Standards, National Electrical Code (NEC), Tucson-Pima County Outdoor Lighting Code (OLC), International Building Code 2018 (IBC)
PERMIT STATUS: PARTIAL APPROVAL - PLEASE ADDRESS FOLLOWING ITEMS FOR PERMIT RECORD
1. UDC:
A) revise site frontage on application and on the location plan to 147 feet per city's GIS mapping system
B) landlord approval required, but not found within package - provide an email or letter from the property management, please
2) NEC / OLC -
A) add note that signs shall shut off by midnight curfew via timer
B) add note indicating location of timer
C) add note indicating location of breaker panel
D) add note indicating dedicated circuits will be labeled
3) IBC:
A) provide size of mounting bolts and number for each wall sign
Send revisions to Heather.Thrall@tucsonaz.gov |
| 03/07/2023 |
COT - ENGR - Signage Final |
|
Passed |
|