Case: T22DV03991

Parcel: 133369540

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
07/14/2022 INSP - INITIAL CODE ENFORCMENT Approved ACTIVE LEAK IN THE WALL BETWEEN THE LIVING ROOM AND MAIN BEDROOM
WATER BUBBLE AT THE WALL/ROOF JOINT IN THE LIVING ROOM
WATER LEAKING FROM THE BOTTOM OF THE ELECTRICAL PANEL. ABLE TO HEAR DRIPPING WITHIN THE PANEL ALREA
FLOORING IN THE MAIN BEDROOM IS WET
UNABLE TO DETERMINE IF LEAK IS FROM A FAULTY ROOF OR POSSIBLY FROM A A/C DRAIN LINE SINCE THE AIR HANDLER IS NEXT TO THE ELECTRICAL PANEL
UNABLE TO REMOVE PANEL TO CHECK FOR ANY IMMEDIATE HAZARDS. FOUND NO CURRENT READINGS ON THE PANEL

MET WITH REGIONAL MANAGER. DISCUSSED ISSUES AND ABATEMENT OPTIONS. IF AN ELECTRICIAN CANNOT EVALUATE IMMEDIATELY THEN POWER SHALL BE SHUT OFF AT THE METER UNTIL AN ELECTRICIAN CAN EVALUATE.

VALUE ELECTRIC ON SITE. NO WATER INTRUSION ON BUS BARS OR ANY OTHER ELECTRICAL COMPONENTS
MAINTENANCE REPAIRED ISSUE. CLOGGED FILTER AND CONDENSATION LINE. LEAK STOPPED. MAINTENANCE TO LEAVE OPEN FOR 24 HOURS TO DRY THE AREA.
ISSUE RESOLVED