Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/14/2022 | INSP - INITIAL CODE ENFORCMENT | Approved | ACTIVE LEAK IN THE WALL BETWEEN THE LIVING ROOM AND MAIN BEDROOM WATER BUBBLE AT THE WALL/ROOF JOINT IN THE LIVING ROOM WATER LEAKING FROM THE BOTTOM OF THE ELECTRICAL PANEL. ABLE TO HEAR DRIPPING WITHIN THE PANEL ALREA FLOORING IN THE MAIN BEDROOM IS WET UNABLE TO DETERMINE IF LEAK IS FROM A FAULTY ROOF OR POSSIBLY FROM A A/C DRAIN LINE SINCE THE AIR HANDLER IS NEXT TO THE ELECTRICAL PANEL UNABLE TO REMOVE PANEL TO CHECK FOR ANY IMMEDIATE HAZARDS. FOUND NO CURRENT READINGS ON THE PANEL MET WITH REGIONAL MANAGER. DISCUSSED ISSUES AND ABATEMENT OPTIONS. IF AN ELECTRICIAN CANNOT EVALUATE IMMEDIATELY THEN POWER SHALL BE SHUT OFF AT THE METER UNTIL AN ELECTRICIAN CAN EVALUATE. VALUE ELECTRIC ON SITE. NO WATER INTRUSION ON BUS BARS OR ANY OTHER ELECTRICAL COMPONENTS MAINTENANCE REPAIRED ISSUE. CLOGGED FILTER AND CONDENSATION LINE. LEAK STOPPED. MAINTENANCE TO LEAVE OPEN FOR 24 HOURS TO DRY THE AREA. ISSUE RESOLVED |