Case: T22DV00431

Parcel: 11504480A


Addresses:

1020 N TYNDALL AV


Inspection Status: Passed

Inspection History: COT - ENFC - Code Enforcement - Follow Up

Case Number - T22DV00431

Inspection Description - COT - ENFC - Code Enforcement - Follow Up

Inspection Status - Passed

Date Description Inspector Results Comments
09/07/2022 COT - ENFC - Code Enforcement - Follow Up Passed {Activity date: 09/07/2022; Status: Approved; Inspector: VALDEZ; Comment: Entered by VALDEZ - 9/07/2022 FOLLOW UP INSPECTION RESULTS: ONSITE INSPECTION RESULTS:
1ST FLOOR: ALL ELEVATORS ARE FUNCTIONING, GARBAGE SERVICE FROM WASTE MANAGEMENT CONTINUES.
REQUIRED REPORTS TFD REPORTS
" FIRE ALARM SYSTEM
" FIRE SPRINKLER SYSTEM PROVIDED TO TFD ABATED
" PROVIDE FIRE EXTINGUISHERS
" EXIT/ EMERGENCY EGRESS LIGHTING
" GENERATOR SYSTEM PROVIDED TO TFD ABATED
" FIRE PUMP

CONCERNS: WATER LEAK OUTSIDE OF THE THE FIRE PUMP ROOM, GARAGE LEVEL, SOURCE IN UNKNOWN


GREEN / ABATED ON 9-07-2022 INSPECTION ABATED

LOWER LEVEL /LL GARAGE
" MAINTENANCE SUPERVISOR OFFICE, MISSING FIRE SPRINKLER
" MISSING COVER PLATE TO JUNCTION BOX ABATED
" EXTENSION CORD BEING USE IN LIEU OF PERMANENT WIRING
" FOUR MISSING OR DAMAGED EXIT SIGNS IN PARKING GARAGE (P1) NOT LAMINATED
STORAGE ROOM
SPRINKLER CLEARANCE VIOLATIONS DUE TO EXCESSIVE STORAGE
ELEVATOR LOBBY EXIT SIGNS MISSING OR DAMAGED ABATED

TRASH COMPACTOR ROOM:
" SHEETROCK DAMAGE ABATED
" FIRE EXTINGUISHER NOT PROPERLY MOUNTED
" GAS CAN INSIDE THE ROOM ABATED

GARAGE LEVEL
" FIRE PUMP LEAKING (LEAK CONTINUES SOURCE IS UNKNOWN)
" MISSING EXIT SIGNS
2ND FLOOR
" FLOOR LITTER INSIDE DOORS OF THE TRASH CHUTE

" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" SHEETROCK DAMAGE
" STAIRWELL LIGHTING INOPERABLE
3RD FLOOR
" FLOOR LITTER INSIDE DOORS OF THE TRASH CHUTE
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY SECURED
4TH FLOOR
" FLOOR LITTER INSIDE DOORS OF THE TRASH CHUTE
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED
" PORTABLE FIRE EXTINGUISHER NOT CODE COMPLIANT
" MISSING OR DAMAGED LIGHT COVERS
" LITTER IN ELECTRICAL ROOM
5TH FLOOR
" LITTER IN STAIRWELL ABATED
" FLOOR LITTER INSIDE DOORS OF THE TRASH CHUTE
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED
" PORTABLE FIRE EXTINGUISHER NOT CODE COMPLIANT (2)
" MISSING OR DAMAGED LIGHT COVERS
" HALLWAY LIGHTS INOPERABLE
6TH FLOOR
" STAIRWELL LIGHT INOPERABLE
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED
" FLOOR LITTER INSIDE DOORS OF THE TRASH CHUTE
" MULTIPLE SPRINKLER COVERS MISSING ABATED
7TH FLOOR
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED
" ELECTRICAL ROOM WITH AND OPENING JUNCTION BOX, EXPOSED WIRING
" ELEVATOR LOBBY HAS ONE LIGHT BURNED OUT.
" MISSING OR DAMAGED LIGHT COVERS
" STAIRWAY #2 MISSING HANDLE FOR FDC ABATED
" OPEN JUNCTION BOX IN CEILING OUTSIDE ROOM #706
" FIRE EXTINGUISHER NOT DATED
8TH FLOOR
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED ABATED
" MISSING OR DAMAGED LIGHT COVERS
" FIRE EXTINGUISHER NOT DATED (2)
9TH FLOOR
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS BATTERY INOPERABLE ABATED
" ELEVATOR LOBBY HAS ONE LIGHT BURNED OUT.
" MISSING OR DAMAGED LIGHT COVERS
10TH FLOOR
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" ALARM STROBE BROKEN
" MISSING OR DAMAGED LIGHT COVERS
" MULTIPLE SPRINKLER COVERS MISSING ABATED
" FIRE EXTINGUISHER NOT DATED
" STAIRWAY #2 FDC HANDLE MISSING ABATED

11TH FLOOR
" LIGHT FIXTURES NOT PROPERLY MOUNTED AND SECURED
" MISSING OR DAMAGED LIGHT COVERS
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED OR INOPERABLE ABATED
" FIRE EXTINGUISHER NOT DATED (2)
12 FLOOR
" LIGHT FIXTURES NOT PROPERLY MOUNTED AND SECURED MISSING BULBS
" MISSING OR DAMAGED LIGHT COVERS
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" EXIT SIGNS NOT PROPERLY MOUNTED AND SECURED OR INOPERABLE
" MISSING EXIT SIGNS
" FIRE SPRINKLER COVERS MISSING (2) ABATED
13TH FLOOR
" THE ELECTRICAL ROOM HAS CONDUIT AND PENETRATIONS OR OPENINGS NOT SEALED WITH FIRE CAULKING
" 3 OUT OF 4 FIRE EXTINGUISHER ARE DISCHARGED
" MISSING OR DAMAGED LIGHT COVERS
" MULTIPLE SPRINKLER COVERS MISSING ABATED
" STAIRWELL #2 LIGHTS INOPERABLE
14TH FLOOR
" STAIRWELL LIGHT BURNED OUT
" ELECTRICAL ROOM HAS OPEN JUNCTION BOX WITH EXPOSED WIRING
" FIRE EXTINGUISHER ARE DISCHARGED
GYM HALLWAY
" HALLWAY ELECTRICAL PANEL OBSTRUCTED BY WALL ART ABATED
JANITORS ROOM
" 3 DISCONNECTS NO LABELING AND OBSTRUCTED
" SHEETROCK DAMAGE ABATED
" LITTER IN ROOM ABATED
STEAM ROOM
" RUST ON THE SPRINKLER ESCUTCHEON
RESTROOM
" SHEETROCK DAMAGE ABATED
" SPRINKLER COVERS MISSING
ROOF
" STAIRWELL HAS BURNED OUT LIGHT
" EASTSIDE ON THE DECORATIVE ROCK AREA IS FILLED WITH ANIMAL WASTE / 9/07/2022 UNABLE TO INSPECT. NO ACCESS.
" CONCRETE WALL HAS OPEN CONDUIT WITH EXPOSED WIRING / 9/07/2022 UNABLE TO INSPECT. NO ACCESS.
" 2 UPPER POOL ARE UNSANITARY ABATED
" DECK BOARDS ON BOTH UPPER AND LOWER DECKS ARE LOOSE AND UNEVEN
" OUTDOOR GAS GRILL IS MISSING GAS SHUT HANDLE
" OUTDOOR GRILL AREA MISSING FIRE EXTINGUISHER
" FDC SIGN MISSING
CHLORINATION ROOM
" 4 POOL MOTOR WITH DAMAGED PVC FITTINGS EXPOSED WIRING
" 1 SPA MOTOR WITH DAMAGED PVC FITTING WITH EXPOSED WIRING
MECHANICAL ROOM
" 1 BOILER INOPERABLE (LEADER) LEADER WORKING BUT MEMBER INOPERABLE
" MISSING COVER PLATE ON OVERHEAD JUNCTION BOXES
" DRILL HOLE IN A JUNCTION BOX ABATED
" EXPOSED WIRING
ROOF TOP CHILLER ZONE
" EAST CHILLER IS INOPERABLE
ELECTRICAL PANELS
" PANELS RL.RH,ELR HAVE NO PANEL SCHEDULE
" OBSTRUCTED BY BROKEN FURNITURE
} ; {Activity date: 08/24/2022; Status: Approved; Inspector: VALDEZ; Comment: Entered by VALDEZ - ONSITE INSPECTION ALL ELEVATORS WERE OPERATIONAL. THE ENTRANCE TO THE POOL / ROOF IS CLOSED FOR REPAIRS DECK BOARDS LOOSE BUT THE POOL WAS CLEAN. THE CORRIDORS HAVE LARGE BOXES WHICH WON'T FIT IN THE TRASH CHUTES. THERE ARE NO EGRESS ISSUES IN THE CORRIDORS I ENTERED. LIGHT HAS IMPROVED IN THE STAIRWAYS. MYSELF AND CHRIS GATES FROM TFD WILL BE CONDUCTING A FOLLOW UP INSPECTION ON SEPT 7, 2022. THERE IS A HEARING SET FOR OCTOBER 4, 2022 AT 10:00 AM.} ; {Activity date: 08/24/2022; Status: Approved; Inspector: VALDEZ; Comment: Entered by VALDEZ - TFD REPORT ON AN ONSITE INSPECTION:
Fire Alarm (currently has some deficiencies)
Automatic Fire Sprinkler/ Standpipe systems (was provided but the system has deficiencies that I don't if they have been repaired)
Emergency Generator (was provided but the system has deficiencies that I don't if they have been repaired)
Fire Pump (have not received)
Fire Extinguishers (have not received)
Exit/ Emergency egress lighting (have not received)} ; {Activity date: 08/23/2022; Status: