Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSEL - Electrical Final | Re-inspection required | 10/26/23: electrical circuits for garbage disposal, laundry room and exterior receptacles not working. Missing receptacle for double vanity at master bedroom. Clean outs on west side of home need to be cut to grade. Uni strut for gas line is not securely fastened to house. Bonding is required for gas (and water if not pex but pex is not indicated inside of main panel at this time) | ||
| 10/27/2023 | COT - RSEL - Electrical Final | Passed | 10/26/23: electrical circuits for garbage disposal, laundry room and exterior receptacles not working. Missing receptacle for double vanity at master bedroom. Clean outs on west side of home need to be cut to grade. Uni strut for gas line is not securely fastened to house. Bonding is required for gas (and water if not pex but pex is not indicated inside of main panel at this time) 10/27/23: corrections made. |