Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - HCEL - Outdoor Lighting
Permit Number - T22CM07804
Inspection Description - COT - HCEL - Outdoor Lighting
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2025 | COT - HCEL - Outdoor Lighting | Re-inspection required | 10/8/25: Refrigerant lines must be wrapped for UV Protection, Verify proper amperage at disconnect boxes for all (HVAC,Evap,Hood,Cooler), all exterior receptacles must be GFCI and WR, proper covers for exterior receptacles, hard cap water supply line at upstairs stairwell, properly terminate low voltage cables at raceway, clearance at upstairs walk way must be 32" wide minimum, all exterior water supply lines must be insulated and coated for UV Protection, all receptacles at kitchen must be GFCI, any receptacle within 6' of water source must be GFCI, vacuum breaker required at mop sink and exterior supply line, panic hardware required at egress gate at enclosed area, all site work must be completed prior to issuance of TCO, restrooms must be completed, all sinks require knee guards, towel dispenser and soap dispenser shall not be higher than 48" above finish floor, cooler/freezer must be functional, mix valves at sinks must be installed. MC cable must be rated for outdoor use. Labels at egress doors must state that doors must remain unlocked while occupied. Secure kitchen equipment. More Items may be added. | |
| 10/31/2025 | COT - HCEL - Outdoor Lighting | Passed |