Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/25/2023 |
COT - RSEL - Electrical Final |
|
Re-inspection required |
Denied, #6 cu wire size from Gateway panel, Disconnect, DG Meter and Power-wall panel should be #4cu per approved revised plans (see attachment) |
| 05/02/2023 |
COT - RSEL - Electrical Final |
|
Passed |
|