Inspection History Details
Inspection Status: Canceled
Inspection History: RSEL - Electrical Progress
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2025 | RSEL - Electrical Progress | Canceled | ||
| RSEL - Electrical Progress | Re-inspection required | 10-28-25: wrap all copper lines with R3 insulation, exterior receptacles must be weather resistant, seal exterior wall where pressure relief valve exits wall prevent infestation, seal all holes in water heater closet and correct tear in awg wire, paint all exterior plastics on rooftop, replace kitchen & dining breakers to arch fault & update breaker labeling to include living room, add shackle to water heater breaker, missing vacuum breaker on hose bib, missing hammer arrestor on dishwasher line, seal water closet. | ||
| 11/05/2025 | RSEL - Electrical Progress | Passed | 11/5/25 All corrections made. |