Permit: T22CM06674

Parcel: 123100280


Addresses:

1625 N CAMPBELL AV


Inspection Status: Partial Pass

Inspection History: COT - HCME - Mechanical Above Ceiling

Permit Number - T22CM06674

Inspection Description - COT - HCME - Mechanical Above Ceiling

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/04/2024 COT - HCME - Mechanical Above Ceiling Partial Pass SMACNA pressure testing for ductwork in space serviced by ERU 201/202 approved. Okay to insulate. 1/4/2024
01/10/2024 COT - HCME - Mechanical Above Ceiling Partial Pass Main Exhaust Ductwork for AHU 211 - Tower 3 - SMACNA pressure test approved. Okay to insulate. 1/10/2024
01/31/2024 COT - HCME - Mechanical Above Ceiling Partial Pass Mechanical piping from area A tower 3 space up the shaft to the low roof under pressure. 1/31/2024
02/22/2024 COT - HCME - Mechanical Above Ceiling Canceled Canceled per contractor. 2/22/2024
05/03/2024 COT - HCME - Mechanical Above Ceiling Not Ready
05/06/2024 COT - HCME - Mechanical Above Ceiling Partial Pass Area A, Ok to place ceiling tiles.
10/19/2023 COT - HCME - Mechanical Above Ceiling Partial Pass 10/18/23 preamp room 14513 ok to drywall ceiling
10/25/2023 COT - HCME - Mechanical Above Ceiling Partial Pass 10/18/23 preamp room 14513 ok to drywall ceiling
10/25/23: hydro pressure test at 150psi at HHW and CHW to AHU 009 Basement Tower 4. Ok to insulate
11/13/2023 COT - HCME - Mechanical Above Ceiling Partial Pass 10/18/23 preamp room 14513 ok to drywall ceiling
10/25/23: hydro pressure test at 150psi at HHW and CHW to AHU 009 Basement Tower 4. Ok to insulate
11/13/23: Above ceiling hydronic pipe Tower 3 Area A, HHW piped to VAV's throughout Tower 3 Area A(Pressure Test), CHW pipe to FCU's to IDF room and Freezer room Tower 3 Area A (Pressure Test).
11/15/2023 COT - HCME - Mechanical Above Ceiling Partial Pass 11/15/23 duct pressure test tower 3 as reflected on attached photos this date Supply Air Main Ductwork SMACNA pressure Testing - Tower 3 - Area A Above Ceiling
11/30/2023 COT - HCME - Mechanical Above Ceiling Partial Pass 10/18/23 preamp room 14513 ok to drywall ceiling
10/25/23: hydro pressure test at 150psi at HHW and CHW to AHU 009 Basement Tower 4. Ok to insulate
11/13/23: Above ceiling hydronic pipe Tower 3 Area A, HHW piped to VAV's throughout Tower 3 Area A(Pressure Test), CHW pipe to FCU's to IDF room and Freezer room Tower 3 Area A (Pressure Test).
11/15/23 duct pressure test tower 3 as reflected on attached photos this date
11/30/23: mechanical above ceiling in Area B passed (south of passage 13572S), pending Rooms 14518 and storage
12/14/2023 COT - HCME - Mechanical Above Ceiling Partial Pass Area C. All MEP’S above ceiling approved.
EVS ROOM #14550. Tower 4 Area B MEP’S all above ceiling approved.
#14518 AREA B (GLASS WASHROOM) MEP’S all above ceiling approved. 12/14/2023