Permit: T22CM05873

Parcel: 123072210


Addresses:

2316 E HELEN ST

Inspection Status: Re-inspection required

Inspection History: RSBU - Building FinalĀ 

Date Description Inspector Results Comments
03/17/2025 RSBU - Building FinalĀ  Re-inspection required 17 Mar 25
1. Outdoor receptacle needs to be Weather rated; will have a "WR" stamped on the front. The outlet in bathroom is WR rated maybe switch that one out with the exterior.
2. The circuits are not labeled in the main pain.
3. Mini split calls for 15 amp max CB.