Inspection History Details
Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2026 | RSBU - Building Final | Re-inspection required | 1/12/2026 per previous notes. Missing disconnects at all mini splits. | |
| 02/20/2026 | RSBU - Building Final | Passed | ||
| 04/29/2025 | RSBU - Building Final | Re-inspection required | Outside receptacles need to be WR The plug needs to be WR Any receptacle in laundry room GFI Arc - Fault breakers at all living spaces Label the sub panel Support the expansion tank in the water heater The lights outside patio not turning on Check smoke detector is making noise Burried receptacle in storage room Burried receptacle in hallway next to storage room Kitchen- install GFI outlets. Minimum 2 circuits Swap the WR outlets in the kitchen to outside GFI - garbage disposal We Hammer arrestor on the hot side Anti tip for the stove We need receptacles in the island Burred receptacle entrance hallway (front of the house) Plans call for 2 islands Bath 1 jack and Jill on the original plans. -All bedrooms have sliding doors on plans ⁃ Min one receptacle on a 10 ft wall Cancel 2 receptacles. (The plans have 3 outlets) should be 1 Master bdrm- relocate closet on plans. Outside- Swap all mini splits - no UL Listings All made in Mexico Anti siphon at hose bibs Screw cap on the outside Insulate and secure the outside water pipe Label the panel KO seal on the bottom of the panel Box outside on the roof needs to be sealed close the hole Missing receptacles outside south side of the house. Every 25 ft Missing exterior light south end. Provide ladder for roof access at final. 4/ |