Inspection Status: Not Ready
Inspection History: COT - LCBU - Building Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - LCBU - Building Progress |
|
Not Ready |
|
| 04/04/2023 |
COT - LCBU - Building Progress |
|
Not Ready |
City approved plans not on site, install address numbers, remove flexible drain, GFCI outlet at bathroom & fountain, install pan at water heater, restroom has several ADA non compliant issues, install two GFCI outlets at the island |
| 04/07/2023 |
COT - LCBU - Building Progress |
|
Re-inspection required |
4-7-23: 1-Bathroom fixtures/accessible units are not per approved plans/Code. 2-Toilet seat is not open front. 3-Receptacles/ dedicated circuit missing for KitchenIsland. |