Inspection History Details
Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2022 | RSBU - Building Final | Not Ready | ||
| 09/07/2023 | RSBU - Building Final | Re-inspection required | Provide approved plans to view the scope of work that's been done. 9/7/2023 | |
| 09/11/2023 | RSBU - Building Final | Re-inspection required | Provide approved plans to view the scope of work that's been done. 9/7/2023 9/11/23: install house address numbers, cut clean outs in front yard to grade, long kitchen counter requires 2 additional outlets, exposed flex duct in garage ceiling is not allowed.Remove all flex duct in garage and install hard metal duct. |
|
| RSBU - Building Final | Passed | 10-4-23: House numbers have been installed on front of garage, clean-outs have been cut to match grade with screw caps installed, exposed flex duct has been replaced with metal duct, and the kitchen is not part of the remodel so additional outlets were not needed. Okay to issue Certificate of Completion. |