Inspection Status: Not Ready
Inspection History: COT - LCPL - Plumbing Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - LCPL - Plumbing Progress |
|
Not Ready |
|
| 10/20/2022 |
COT - LCPL - Plumbing Progress |
JBURGE |
Partial Approval |
Entered by NGARCIA3 - Partial. Main domestic water line ; 8" with 2 shut off valves at North and East side of the play area. Approximately 175 linear feet. Ok to cover progress areas. |
| 03/01/2023 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
3/1/23 partial approval for mechanical room water risers 4 each penetrations through exterior masonry wall to approximately 2’ stub out, ok to cover |
| 06/12/2023 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
Plumbing for new sloth enclosure. |
| 08/21/2023 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
8/21/23: CU domestic water line for Ramada misters and 3 hose bibs of to cover, tested at 100psi air. |
| 10/19/2023 |
COT - LCPL - Plumbing Progress |
|
Passed |
|
| 12/07/2022 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
partial approval for connection from main site sewer to 3 ft from building |