Inspection Status: Not Ready

Inspection History: COT - LCPL - Plumbing Final 

Permit Number - T22CM01451

Inspection Description - COT - LCPL - Plumbing Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/26/2022 COT - LCPL - Plumbing Final  Not Ready
10/06/2022 COT - LCPL - Plumbing Final  DBENOIT Prior to Final Inspectn Entered by DBENOIT1 - WATER CHLORINATION REPORT REQUIRED PRIOR TO FINAL INSPECTION.
04/05/2024 COT - LCPL - Plumbing Final  Re-inspection required 4/5/24: all of building 3 is missing (insulation at water heaters, air gap required at condensate drain in laundry room, dishwashers not installed, T-tops missing on roof for dryer vent, UV coat plastic piping at roof, window locks), ADA unit missing (circuit at kitchen, panel schedule, bathroom and kitchen guards under sink), Unit 3208 missing lock out breaker for water heater, Unit 3207 bank plate missing at panel, Unit 3205 no power at kitchen circuit, Unit 3103 Condensate drain for A/C unit not ran, Unit 3104 water heater is not wired, Unit 3202 GFCI at kitchen not functioning properly, Unit 3301 Kitchen receptacle hot and neutral reversed and condensate not complete. Missing vent grills at breezeways.
04/11/2024 COT - LCPL - Plumbing Final  Passed