Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2022 |
RSBU - Building Final |
|
Not Ready |
|
| 08/05/2025 |
RSBU - Building Final |
|
Passed |
Passed 8/5/25. Cutover to new 400ah panel delayed pending TEP installing new transformer and relocating telephone poles, customer temporarily wiring addition to existing 200ah panel that can handle additional load |
| 08/14/2025 |
RSBU - Building Final |
|
Canceled |
|
| 11/25/2025 |
RSBU - Building Final |
|
Re-inspection required |
11-25-25: missing hammer arrestors at washer/dryer, install bubble covers at all exterior receptacles-receptacle covers must rated heavy duty while in use, paint all exterior plastic, install receptacle/bubble covers must rated at exterior side adjacent to mini split, seal/paint all exterior wood, missing arch fault breakers- arch faults are required in every habitable spaces, replace 70amp breaker at main with a 100 amp breaker, missing smoke detector in bedroom-must be hardwired, nm cable feeding can lights are not allowed in wet locations-refer to architect if record for fix & provide updated RFI, mini split is over amped-max breaker is 25amps. |
| 12/05/2025 |
RSBU - Building Final |
|
Passed |
12/5/25 CORRECTIONS MADE |