Inspection Status: Passed
Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.
| Date |
Description |
Inspector |
Results |
Comments |
| 08/26/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
WGALLAGHER |
Approved |
Entered by NGARCIA3 - Approved |
| 08/08/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
JBURGE |
Partial Approval |
Entered by NGARCIA3 - Partial. Electric only. Remove trash from inside of building; fire hazard. |
| 08/04/2022 |
COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. |
DMUNIZ |
Correction Required |
Entered by NGARCIA3 - corrections required, missing receptacle outlet in hall where 10’ is exceeded. Missing receptacle outlet in bedroom to meet 6’ -12’ rule. |