Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2022 | FIRE - ALARM FINAL | Approved | ||
| 03/01/2022 | FIRE - ALARM FINAL | Partial Approval | -Need to test AOR 2 way communication -Horn in unit 101 bedroom not working (new device on backorder) -Verify that battery on dialer reports trouble signal -Provide copy of NFPA 72 ROC when complete -Provide copy of elevator commision testing report |