Permit: T21CM08893

Parcel: 137040040

Inspection Status: Not Ready

Inspection History: RSBU - Building Final 

Permit Number - T21CM08893

Inspection Description - RSBU - Building Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 RSBU - Building Final  Not Ready
05/09/2024 RSBU - Building Final  Re-inspection required PARTIAL PENDING OTHER INSPECTIONS. 11/29/2023
5/9/24: T-top missing at kitchen exhaust, new kitchen outlets must be GFCI, water hammer arrestor missing at washer, all exterior abandoned electrical boxes must have faceplates, electrical whip at A/C unit not being supported off of roof, A/C unit is being under Amped (41Amp min and 60Amp max), all exterior plastic piping must be UV coated.
10/02/2024 RSBU - Building Final  Passed All corrections were made. Approved. 10/2/2024
11/28/2023 RSBU - Building Final  Not Ready
11/29/2023 RSBU - Building Final  Partial Pass PARTIAL PENDING OTHER INSPECTIONS. 11/29/2023