Permit: T21CM08148

Parcel: 140264770

Inspection Status: Not Ready

Inspection History: COT - RSPL - Plumbing Final 

Permit Number - T21CM08148

Inspection Description - COT - RSPL - Plumbing Final 

Inspection Status - Not Ready

Date Description Inspector Results Comments
10/27/2022 COT - RSPL - Plumbing Final  Not Ready
04/12/2024 COT - RSPL - Plumbing Final  Re-inspection required 6/22/23: homeowner informed that they need contractor make a letter stating they are taking responsibility for the addition for the life of the property. ROC# must be present and active on letter.

7/20/23: Remove sheet rock to expose work done.

7/26/23: Structural Electrical Plumbing HVAC error issues. Remove ALL drywall and insulation for full thorough inspection.

4/12/24: hot and neutral reversed at bathroom GFCI, drain at bathroom lav must be smooth material, exterior GFCI must be WR, lock out caps missing at A/C unit, Arc-fault breaker's missing at multiple locations.
05/17/2024 COT - RSPL - Plumbing Final  Passed 5/17/24: Letter has been submitted by contractor taking full responsibility of addition for the life of the property and will be liable for all work done. See letter in attachments.
COT - RSPL - Plumbing Final  Re-inspection required
07/20/2023 COT - RSPL - Plumbing Final  Re-inspection required 7/20/23: Remove sheet rock to expose work done.
07/26/2023 COT - RSPL - Plumbing Final  Re-inspection required 7/26/23: Structural Electrical Plumbing HVAC error issues. Remove ALL drywall and insulation for full thorough inspection.