Permit: T21CM07236

Parcel: 117091080


Addresses:

1121 S 11TH AV

Inspection Status: Not Ready

Inspection History: COT - LCBU - Building Progress

Date Description Inspector Results Comments
10/26/2022 COT - LCBU - Building Progress Not Ready
05/11/2026 COT - LCBU - Building Progress Partial Pass ok to proceed on stucco
08/12/2026 COT - LCBU - Building Progress Not Ready
09/01/2026 COT - LCBU - Building Progress Partial Pass 9-1-26: MEP progress inspection on unit's 10-firecaulk feeder penetrations at decking & above ceiling, strap mini split feeders, insulate hot pet lines 3/4" and larger, add plastic bushings at sub panels, block block party walls at wall gaps, 8-same notes, cou-le of units on 2nd floor-ground pancake box, putty pack required at party walls when receptacles are within 2' from each other, strap/secure exhausts within 2' of a bend and at 4' intervals thereafter, plastic bushings at panel and insulation of hot pex lines, seal penetrations at top plates, decking and at party walls.
10/09/2026 COT - LCBU - Building Progress Re-inspection required Here are the notes from today.

10/9/26: Dryers duct cannot be double wall pipe per IMC and manufacturer requirements. Dryers cannot share dryer Duct ( 1st and 2nd floor unit) cannot tie into (3rd and 4th unit). Exhaust fans must be UL listed and shall have appropriate sized duct. Revision required for mechanical modifications. 5-sided gypsum box required at refrigerator boxes .