Permit: T21CM07236

Parcel: 117091080


Addresses:

1121 S 11TH AV

Inspection Status: Not Ready

Inspection History: COT - LCME - Mechanical Intermediate

Date Description Inspector Results Comments
10/26/2022 COT - LCME - Mechanical Intermediate Not Ready
09/18/2026 COT - LCME - Mechanical Intermediate Re-inspection required 9/18/26: DRYER VENT HAS BEEN TIED TO KITCHEN EXHUST + BATHROOM EXHAUST (Please have all exhaust running independently and properly terminated and sized), AH-1 REQUIRE PER PLANS ABOVE DROP CEILING IN BATHROOM, EXHUST FAN MISSING AT LAUNDRY ROOM AREA, mechanical plans not per approved plans, pending other items called out on previous inspections.