Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Not Ready
Inspection History: COT - LCPL - Plumbing Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - LCPL - Plumbing Progress |
|
Not Ready |
|
| 03/25/2026 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
Partial pass. 2" domestic water line in place and under pressure. Okay to backfill all progress areas. Ensure blue caution tape is in place after first lift of compaction. 3/25/2026 |
| 07/23/2025 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
Interior underground plumbing at sewer and lateral lines. Ok to cover progress areas. |
| 09/01/2026 |
COT - LCPL - Plumbing Progress |
|
Partial Pass |
9-1-26: MEP progress inspection on unit's 10-firecaulk feeder penetrations at decking & above ceiling, strap mini split feeders, insulate hot pet lines 3/4" and larger, add plastic bushings at sub panels, block block party walls at wall gaps, 8-same notes, cou-le of units on 2nd floor-ground pancake box, putty pack required at party walls when receptacles are within 2' from each other, strap/secure exhausts within 2' of a bend and at 4' intervals thereafter, plastic bushings at panel and insulation of hot pex lines, seal penetrations at top plates, decking and at party walls. |