Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - LCEL - Electrical Progress |
|
Not Ready |
|
| 03/09/2026 |
COT - LCEL - Electrical Progress |
|
Partial Pass |
3-9-26: verified trench depth at 4' for a 4" Schedule 40 electric conduit for a transformer tie in together with a 2" cox communication conduit running west to east on north side of building. Okay to backfill approximately 340' of open trench. |