Permit: T21CM06279

Parcel: 120084140


Addresses:

150 W OKLAHOMA ST

Inspection Status: Not Ready

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
10/27/2022 COT - RSME - Mechanical Final  Not Ready
09/27/2022 COT - RSME - Mechanical Final  TGAUSP Not ready for Inspection Entered by NGARCIA3 - NR
08/08/2022 COT - RSME - Mechanical Final  SCARRAZCO Not ready for Inspection Entered by VVERA1 - not ready.
02/25/2026 COT - RSME - Mechanical Final  Re-inspection required 2-25-26: insulate hot copper line at tankless water heater, install vacuum breaker at hose bibs, install cover plate above ceiling at bedroom 2, seal water closets, missing hammer arrestees at laundry room, missing hammer arrestor at refrigerator line, and at dishwasher, install stove with anti tip device, lower thermostat height to 48" o.c. ( this is required per City of Tucson-Inclusive Home). Missing ceiling fans in all bedrooms & living room, remove covers from all smoke detectors, reschedule a SWG pressure test/clearance because it's been over 6 months and meter was never requested by customer, exterior receptacles require a bubble covers, arch fault breakers required for habitable spaces including, living rooms, hallways, bedrooms, kitchens. Paint exterior vent at rooftop, a/c is over amped, install a permanent label at rooftop disconnect.
04/07/2026 COT - RSME - Mechanical Final  Passed
06/24/2025 COT - RSME - Mechanical Final  Re-inspection required 6/24/25
1. Primary bedroom receptacles are wired improperly, open ground, reverse hot/neutral.
2. Hallway receptacle across from bathroom has open ground.
3. Kitchen outlet across from fridge has open ground.
5. Water hammer arrestors needed at ice maker and laundry washer machine water inlets.
6. Receptacles in pantry and just outside pantry has open hot.
7. Bedroom 2 all receptacles, hot/neutral reversed.
8. Bedroom 2 is missing receptacle on the right wall as you walk in.
9. Bedroom 3 all receptacles hot and neutral reversed.
10. Bedroom 4; smoke detectors is too close to supply diffuser it sitting 6" away, needs to be minimum of 3 ft away.
11. Bedroom 4; all receptacles hot/neutral reversed.
12. Missing outdoor receptacles front and back of house
13. No plans on site, must have plans available for all inspections
14. T/P line on the water heater needs to terminate no higher than 6" from ground.
15. Provide ladder access to check HVAC.