Inspection History: COT - LCEL - Electrical Underground
Permit Number - T21CM06128
Inspection Description - COT - LCEL - Electrical Underground
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2022 | COT - LCEL - Electrical Underground | Not Ready | ||
05/10/2022 | COT - LCEL - Electrical Underground | JBURGE | Partial Approval | Entered by NGARCIA3 - . Partial. Electric conduits (1” and 3/4” lines) for 8 pole lights. Ok to cover progress areas. |
05/09/2022 | COT - LCEL - Electrical Underground | IVR USER | Cancelled | Entered by IVR USER - IVRS - AP canceled |
01/06/2022 | COT - LCEL - Electrical Underground | JBURGE | Partial Approval | Entered by NGARCIA3 - Partial. Three each secondary conduit lines (3”) from building to future transformer site; approximately 150’. Ok to cover progress areas. Communication lines: 2 each at 2 1/2”from building to North power pole. Ok to cover progress areas. |
01/05/2022 | COT - LCEL - Electrical Underground | IVR USER | Cancelled | Entered by IVR USER - IVRS - AP canceled |
12/16/2021 | COT - LCEL - Electrical Underground | ESTEVENS | Partial Approval | Entered by VVERA1 - Partial. From the SES location to 10 feet out from the building. |
11/12/2021 | COT - LCEL - Electrical Underground | JBURGE | Approved | Entered by VVERA1 - Approved. Primary electric conduits are in place. |
11/02/2021 | COT - LCEL - Electrical Underground | ESTEVENS | Partial Approval | Entered by NGARCIA3 - Partial. Data and communication lines, power lines from SES to interior electrical service panels. |
02/28/2023 | COT - LCEL - Electrical Underground | Partial Pass | 4 of 7 light pole basis. Rebar per plan 20’ coil copper line in place, okay for concrete. | |
03/07/2023 | COT - LCEL - Electrical Underground | Partial Pass | 3/7/23. Light pole base furthest west okay to pour concrete 20' of coil copper line with rebar per plan | |
03/30/2023 | COT - LCEL - Electrical Underground | Canceled | ||
04/28/2023 | COT - LCEL - Electrical Underground | Passed |