Inspection History Details
Inspection Status: Not Ready
Inspection History: COT - LCPL - Plumbing Intermediate
Permit Number - T21CM06028
Inspection Description - COT - LCPL - Plumbing Intermediate
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | COT - LCPL - Plumbing Intermediate | Not Ready | ||
03/17/2023 | COT - LCPL - Plumbing Intermediate | Not Ready | Unit 1. Not ready. Provide DWV test. Staple has punctured ABS line in hall bathroom. Space pex line from any can lights minimum 12”. Exhaust duct needs to be connected in master bedroom. Finish make in receptacles. Add staple to electrical line in kitchen. 3/17/2023 | |
03/23/2023 | COT - LCPL - Plumbing Intermediate | Passed | 3/23/2023 approved. Corrections were made. |