Inspection Status: Passed
Inspection History: COT - LCEL - Construction Power
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2022 |
COT - LCEL - Construction Power |
DQUINN |
Approved |
Entered by NGARCIA3 - Ap
No clearance needed
|
| 07/15/2022 |
COT - LCEL - Construction Power |
TLUNDBERG |
Approved |
Entered by NGARCIA3 - AP |
| 05/10/2022 |
COT - LCEL - Construction Power |
DMUNIZ |
Correction Required |
Entered by NGARCIA3 - corrections required, Provide permanent site address & address tag for SES, Torque and mark all terminations in SES, MDP, & XFMRs. Provide Lock out Tag out for incomplete (120/208v) panels due to procurement issues. Submit approved engineered Alternatives for 120/208v panel changes. Construction meeting was scheduled with COT, TEP, & Construction team to discuss all the following.
|