Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T21CM03549

Parcel: 111051740

Inspection Status: Not Ready

Inspection History: COT - RSPL - Plumbing Final 

Date Description Inspector Results Comments
10/27/2022 COT - RSPL - Plumbing Final  Not Ready
02/03/2022 COT - RSPL - Plumbing Final  NGARCIA Prior to Final Inspectn Entered by NGARCIA3 - sewer receipt required prior to final inspection
07/09/2024 COT - RSPL - Plumbing Final  Re-inspection required 7/9/24: receptacles and light fixtures missing throughout at kitchen area and storage shed. Water closets must be installed at final, kitchen circuits must be GFCI, laundry room circuits must be GFCI, all exterior plastic piping must be UV Coated, refrigerant lines must be UV coated or protected, panel schedules missing throughout, Arc-fault breaker's missing throughout, water hammer arrestor required at dishwasher, service loop at dishwasher must be properly fastened, cover plates missing throughout at receptacles, WR receptacles required on exterior of home, properly terminate all condensation/discharge lines on exterior of home.
07/26/2024 COT - RSPL - Plumbing Final  Passed