Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING PRE-SLAB
Permit Number - T21CM02067
Inspection Description - BUILDING PRE-SLAB
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2021 | BUILDING PRE-SLAB | Approved | ||
06/03/2021 | BUILDING PRE-SLAB | Denied | DE. 1-Live end of tendons have more than 1” exposure to concrete. 2-Tendons need 6” minimum clearance from slab penetrations. |