Inspection Status: Not Ready
Inspection History: COT - LCEL - Electrical Underground
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - LCEL - Electrical Underground |
|
Not Ready |
|
| 08/23/2022 |
COT - LCEL - Electrical Underground |
DQUINN |
Not ready for Inspection |
Entered by NGARCIA3 - nr |
| 03/04/2022 |
COT - LCEL - Electrical Underground |
DQUINN |
Partial Approval |
Entered by VVERA1 - pa
1-4” from pole to trans
4-4” from trans to gear
3-4” from SES to distribution
3-4” from dist to trans switch for generator
Ok to backfill all
|
| 12/07/2021 |
COT - LCEL - Electrical Underground |
DQUINN |
Partial Approval |
Entered by NGARCIA3 - PA
51 - 3/4” conduits and 6 floor boxes ok to backfill at western 1/2 living area |
| 12/02/2021 |
COT - LCEL - Electrical Underground |
TGAUSP |
Cancelled |
Entered by RSALDAT1 - Cancelled
Unable to reach Jose 480-271-2948 for inspection |
| 10/22/2021 |
COT - LCEL - Electrical Underground |
DQUINN |
Partial Approval |
Entered by VVERA1 - Pa
Undergrounds complete from elec room exterior distribution. |
| 10/19/2021 |
COT - LCEL - Electrical Underground |
DQUINN |
Partial Approval |
Entered by NGARCIA3 - pa
From elec room, 1/2 way through building north to SES -
3 - 3/4 “
3 - 1”
6 above conduits for various distribution.
1 - 2” - for parking canopies
4 - 3” for panels A, B, C, and D
1 - 3/4” for hose dryer.
All ok to backfill 1/2 way to SES
|
| 10/15/2021 |
COT - LCEL - Electrical Underground |
DQUINN |
Partial Approval |
Entered by NGARCIA3 - pa
4-4” and 4-2” conduits from mdf room to n ext. ok to backfill.
|
| 10/27/2022 |
COT - LCEL - Electrical Underground |
|
Passed |
|