Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2021 | FIRE - ALARM FINAL | Approved | ||
| 10/29/2021 | FIRE - ALARM FINAL | Partial Approval | approved buildings 6-10. | |
| 10/28/2021 | FIRE - ALARM FINAL | Cancelled | to reopen the permit | |
| 07/28/2020 | FIRE - ALARM FINAL | Prior to Final Inspectn | * SUBJECT TO FIELD VERIFICATION * IF THE RETAIL STORE AREA ENDS UP BEING LEASING OFFICE PLEASE INSTALL A REMOTE ANNUNCIATOR AT THE FRONT DOOR. * THIS PANEL SHALL BE LABELED AS DEDICATED FUNCTION PER NFPA 72 "FIRE SPRINKLER WATERFLOW AND SUPERVISORY SYSTEM" * PER NFPA 72 DRAWINGS SHALL STATE WHEN A SYSTEM IS DEDICATED FUNCTION SO AS BUILT DRAWINGS ARE REQUIRED * PLEASE PRINT 1 FULL SIZE SET FOR THE PROJECT * PROVIDE DOCUMENT BOX AS REQUIRED PER NFPA 72. |