Permit: T20FC00481

Parcel: 12419040F


Addresses:

585 S CHERRY AV

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
11/17/2021 FIRE - ALARM FINAL Approved
10/29/2021 FIRE - ALARM FINAL Partial Approval approved buildings 6-10.
10/28/2021 FIRE - ALARM FINAL Cancelled to reopen the permit
07/28/2020 FIRE - ALARM FINAL Prior to Final Inspectn * SUBJECT TO FIELD VERIFICATION
* IF THE RETAIL STORE AREA ENDS UP BEING LEASING OFFICE PLEASE INSTALL A REMOTE ANNUNCIATOR AT THE FRONT DOOR.
* THIS PANEL SHALL BE LABELED AS DEDICATED FUNCTION PER NFPA 72 "FIRE SPRINKLER WATERFLOW AND SUPERVISORY SYSTEM"
* PER NFPA 72 DRAWINGS SHALL STATE WHEN A SYSTEM IS DEDICATED FUNCTION SO AS BUILT DRAWINGS ARE REQUIRED
* PLEASE PRINT 1 FULL SIZE SET FOR THE PROJECT
* PROVIDE DOCUMENT BOX AS REQUIRED PER NFPA 72.