Case: T20DV03377

Parcel: 11108190B

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
05/15/2020 INSP - INITIAL CODE ENFORCMENT Approved EMERGENCY CALL OUT BY TFD:N/A FROM THE VISUAL INSPECTION. TFD STATED ADJACENT UNIT WAS OK.


ELECTRICAL: WATER HEATER ELEMENT HAS BURNED AND COMPONENTS ARE CHARRED. THE SUB PANEL HAS NO LABELING FOR A WATER HEATER. THE CONDUCTOR SIZE TO THE UNIT IS 14/3 AND ALL BREAKERS IN THE SUB PANEL ARE 20 AMPS.
THE WATER HEATER DATA PLATE READS 4500 WATTS AT 240 VOLTS. ACCORDING TO THIS INFORMATION THE CIRCUIT IS UNDER SIZED, NOT RATED FOR THE CURRENT USE.


PLUMBING: NA


MECHANICAL: MILD SMOKE.


REMARKS: THE UNIT IS CONDEMNED, POWER WAS DISCONNECTED BY TEP. MANAGEMENT WAS ALERTED TO THE FIRE VIA PHONE CONTACT. PERMIT IS REQUIRED FOR REPAIRS