Permit: T20CM09215

Parcel: 14042021A

Inspection Status: Not Ready

Inspection History: COT - HCEL - Electrical Underground 

Date Description Inspector Results Comments
10/26/2022 COT - HCEL - Electrical Underground  Not Ready
05/06/2022 COT - HCEL - Electrical Underground  DMUNIZ Partial Approval Entered by NGARCIA3 - Partial, conduit raceway installed on west side for site light poles ok to backfill progress areas.
11/24/2021 COT - HCEL - Electrical Underground  DMUNIZ Partial Approval Entered by NGARCIA3 - ) Partial, continuation of 4:1-1/4” conduits for site and monument lighting ok to backfill progress areas.
11/12/2021 COT - HCEL - Electrical Underground  DMUNIZ Partial Approval Entered by NGARCIA3 - Partial, 4-(1-1/4”) conduits under slab from West Electrical room location heading East for Site lighting and Sign., ok to backfill progress areas.
11/05/2021 COT - HCEL - Electrical Underground  TGAUSP Partial Approval Entered by RSALDAT1 - Partial for the Secondary conduits at the west side of the building slab, from the proposed transformer location to the gear location
12/20/2022 COT - HCEL - Electrical Underground  Passed