Permit: T20CM07680

Parcel: 118050220

Inspection Status: Not Ready

Inspection History: COT - RSEL - Electrical Final 

Date Description Inspector Results Comments
10/27/2022 COT - RSEL - Electrical Final  Not Ready
02/01/2023 COT - RSEL - Electrical Final  Not Ready missing receptacle on counter top along with one in hallway
island and countertops receptacle needs to be gfi.
washer room needs to be gfi.
open ground in receptacle at entry way north of home.
circuit breaker needs to be change for condenser unit.
electrical panel needs to be labeled
02/10/2023 COT - RSEL - Electrical Final  Passed All electrical outlets are installed and functional. Electrical panel is labeled