Inspection Status: Not Ready
Inspection History: COT - HCPL - Plumbing Progress
| Date |
Description |
Inspector |
Results |
Comments |
| 10/26/2022 |
COT - HCPL - Plumbing Progress |
|
Not Ready |
|
| 10/10/2022 |
COT - HCPL - Plumbing Progress |
JBURGE |
Not ready for Inspection |
Entered by VVERA1 - Not ready. Contractor; will reschedule for 11 October. |
| 10/05/2022 |
COT - HCPL - Plumbing Progress |
JBURGE |
Partial Approval |
Entered by VVERA1 - Partial. 3” waste lines in rooms: 108, 208, 308, 408, 109, 209, 309, 409; 110, 210, 310, 410, 111, 211, 311’ 411 under hydro test.
|
| 07/19/2022 |
COT - HCPL - Plumbing Progress |
DMUNIZ |
Correction Required |
Entered by NGARCIA3 - Corrections required , Provide GAS calcs for 1/2" Gas line 100’-200’ run from 1st floor feeding RTU (1,2,3,4)
|
| 03/03/2023 |
COT - HCPL - Plumbing Progress |
|
Partial Pass |
partial approval for back of house above ceiling ok to insulate |
| 07/25/2023 |
COT - HCPL - Plumbing Progress |
|
Passed |
|
| 11/08/2022 |
COT - HCPL - Plumbing Progress |
|
Partial Pass |
for forth floor domestic water lines pressure test, ok to insulate, excluding A414, A415, A416, A418, A420 AND B414 |
| 11/14/2022 |
COT - HCPL - Plumbing Progress |
|
Passed |
All plumbing lines are under hydronic testing. |
| 11/17/2022 |
COT - HCPL - Plumbing Progress |
|
Partial Pass |
partial approval for 4th floor corridor ok to install drywall |