Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/11/2021 |
ELECTRIC - INTERMEDIATE |
|
Approved |
Approved |
| 06/30/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 1st and 2nd floor sub panels in guest suites inspected and ok to energize. |
| 06/16/2021 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
Corrections required, 2nd floor sub panel inspection. Multiple main breakers have loose connections, missing knockouts on dead fronts require blank spacers. |
| 06/10/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, electrical room 1st floor ok to start fire assembly. |
| 06/03/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 3red floor guest room panels inspected and ok to install dead fronts. |
| 06/01/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, inspection of Electrical panels ok for clearance. |
| 05/27/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 4th floor room panels inspected (419-435). |
| 05/18/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial. Level #1; Lobby area, amenities area, laundry area. Level #4; Room Units 402-414 Room panels. |
| 05/12/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 1st floor rough Electrical in guest rooms complete. |
| 05/11/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, no inspection today see previous notes. |
| 05/10/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, no inspection today see previous notes. |
| 04/30/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 1st floor electrical inspection Of guest rooms North of lobby. |
| 04/28/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, Electrical for East side canopy installed. Fire putty for Electrical boxes in stairwell fire assembly installed. |
| 04/23/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, mechanical room inspected and ok to start Sheetrock. Note: Stairwell Electrical boxes to be Fire rated in ceiling. |
| 04/20/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, staple and fire caulk Romex where needed in mechanical room. |
| 04/15/2021 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
NOT READY CANCELLED BY CONTRACTOR |
| 04/14/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
PARTIAL APPROVAL FOR 2ND FLOOR ROOM INTERIORS EXCLUDING SUB PANELS |
| 04/07/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 3rd and 4th floor stair wells electrical ok. |
| 03/25/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, Electrical progress for 3rd floor ok to proceed. |
| 03/24/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, inspection rescheduled see previous notes. |
| 03/15/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 4th Floor North Guest rooms ok to Sheetrock. |
| 03/10/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial, 4th floor electrical progress. |
| 01/28/2021 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
Partial. Level,#1 Mechanical Room; East and South Electric in walls. Ok to cover. |