Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/11/2021 ELECTRIC - INTERMEDIATE Approved Approved
06/30/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 1st and 2nd floor sub panels in guest suites inspected and ok to energize.
06/16/2021 ELECTRIC - INTERMEDIATE Correction Required Corrections required, 2nd floor sub panel inspection. Multiple main breakers have loose connections, missing knockouts on dead fronts require blank spacers.
06/10/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, electrical room 1st floor ok to start fire assembly.
06/03/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 3red floor guest room panels inspected and ok to install dead fronts.
06/01/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, inspection of Electrical panels ok for clearance.
05/27/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 4th floor room panels inspected (419-435).
05/18/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level #1; Lobby area, amenities area, laundry area. Level #4; Room Units 402-414 Room panels.
05/12/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 1st floor rough Electrical in guest rooms complete.
05/11/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, no inspection today see previous notes.
05/10/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, no inspection today see previous notes.
04/30/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 1st floor electrical inspection Of guest rooms North of lobby.
04/28/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, Electrical for East side canopy installed. Fire putty for Electrical boxes in stairwell fire assembly installed.
04/23/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, mechanical room inspected and ok to start Sheetrock. Note: Stairwell Electrical boxes to be Fire rated in ceiling.
04/20/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, staple and fire caulk Romex where needed in mechanical room.
04/15/2021 ELECTRIC - INTERMEDIATE Not ready for Inspection NOT READY CANCELLED BY CONTRACTOR
04/14/2021 ELECTRIC - INTERMEDIATE Partial Approval PARTIAL APPROVAL FOR 2ND FLOOR ROOM INTERIORS EXCLUDING SUB PANELS
04/07/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 3rd and 4th floor stair wells electrical ok.
03/25/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, Electrical progress for 3rd floor ok to proceed.
03/24/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, inspection rescheduled see previous notes.
03/15/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 4th Floor North Guest rooms ok to Sheetrock.
03/10/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial, 4th floor electrical progress.
01/28/2021 ELECTRIC - INTERMEDIATE Partial Approval Partial. Level,#1 Mechanical Room; East and South Electric in walls. Ok to cover.