Inspection History Details
Inspection Status: Approved
Inspection History: FIREWALL/FIREBARRIER/FIRESTOP
Permit Number - T20CM02530
Inspection Description - FIREWALL/FIREBARRIER/FIRESTOP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Approved | 1080 | |
07/30/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 1st floor corridor above ceiling ok to drop ceiling tiles. | |
07/29/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
06/14/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 4th floor above drop ceiling penetrations inspected and ok to install ceiling tiles. Corrections required for 3rd floor missing fire-stop at penetrations. | |
06/11/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
06/03/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 4th floor South stairwell fire ceiling assembly installed. | |
06/01/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Approved | Approved, 1st floor public area complete. | |
05/27/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Correction Required | Corrections required, first floor public area missing fire stop. | |
05/19/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial approval 1st floor above ceiling grid to bottom of 2nd floor fire barrier in rooms 103 to 113 ok | |
05/12/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 1st floor North guest rooms fire tape complete above ceilings on demising walls. Note: rooms 122 & 131 need fire tape. | |
04/27/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 2nd floor above ceilings for demising walls ok to install ceiling. | |
04/26/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Correction Required | Correction, Remove Sheetrock for inspection of demising wall fire tape above ceiling locations that have not been approved. | |
04/23/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 2nd floor demising walls fire taped from room 222-206. | |
04/23/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
04/22/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
04/06/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 3rd floor Fire stop for demising walls from rooms 301-319. Note: Fire seal any penetrations where missed. | |
04/05/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
03/31/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, 3rd floor demising fire walls Sheet-rocked and ok to tape from Room 322 North. | |
03/30/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
03/15/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, above ceiling and corridor penetrations 4th floor ok to proceed. | |
03/12/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
03/09/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, North 4th floor corridor, fire assembly for ceiling installed. | |
03/08/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
03/04/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, Fire rock for North stairwell 3rd floor installed. (Note: make sure all joints are overlapped where double rock required.) | |
02/10/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Approved | APPROVED FOR 1420 E TUCSON MARKETPLACE BL, 2010(ELECTRICAL UNDERGROUND OUT OF MAIN BLDG TO- -TRANSFORMER PAD) APPROVED, | |
02/09/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
02/05/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | PARTIAL NORTH/SOUTH STAIRWELLS, 4TH FLOOR, 3 RD FLOOR CORRIDOR #324 TO #334 OK TO TAPE | |
02/04/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
02/03/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | PARTIAL - LEVEL 1 NORTH STAIRWELL DOUBLE LAYER SHEET ROCK OK TO TAPE | |
02/02/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | NOT READY CANCELLED BY CONTRACTOR WILL RESCHEDULE 3 FEBRUARY | |
02/02/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
02/01/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | NOT READY ROCK NOT IN PLACE YET | |
02/01/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/29/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level #3; corridor ceiling from room 301-311. | |
01/29/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/28/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level #2; Center Section Corridor at ceiling. | |
01/28/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/27/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/25/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Not ready for Inspection | Not ready. Contractor cancelled | |
01/22/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/21/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level #1; Center Section Corridor; Level #3; Corridor from Room Units 302-311. Progress areas double sheet rocked and fire caulked. | |
01/20/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/19/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level #3; South Corridor from Room Units 301 to 311. | |
01/15/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level #2 Corridor from Unit Rooms 224-234; South Stairwell #2. Progress areas fire caulked. Ok to,cover. | |
01/15/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/14/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
01/13/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial approval 2nd floor rms 224 to 234 cling grid to 3rd floor deck ok to fire tape | |
01/12/2021 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
12/23/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, South Corridor 2nd Floor. Fire barrier for upper walls ok to Proceed on ceiling. | |
12/22/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - AP canceled | |
12/21/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Approved | Partial, North Stairwell 2nd floor ok to proceed with fire wall. North 2nd floor corridor ok to continue with fire barrier installation. | |
12/21/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, North Stairwell 2nd floor ok to proceed with fire wall. North 2nd floor corridor ok to continue with fire barrier installation. | |
12/17/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, North Corridor walls, Ground level ok to continue progress. (Rms 125-135.) | |
12/16/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, South stairwell 2nd floor. Progress on Fire wall ok to proceed. | |
12/15/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, no inspection needed today. | |
12/08/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, North Stairwell Ground level. Fire wall installed and ok to Tape & proceed. | |
12/07/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, South End corridor on Ground level, mechanical penetrations sealed and ok to Sheetrock ceiling. | |
12/04/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | PARTIAL, no inspection today. | |
12/02/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial, Top of Fire assembly on South end, Ground level Corridor Walls. Ok to continue, and Fire tape progress areas. (South Stairwell to Room 110). | |
12/01/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Partial Approval | Partial. Level 1. Two layers of Sheet rock between south stairwell and unit. | |
11/30/2020 | FIREWALL/FIREBARRIER/FIRESTOP | Cancelled | IVRS - RI canceled |